Home > Prodotti > Strumenti da processo > Regolatori > pH Analog Controller with Self-Diagnostic Test – HI8710

SKU: HI8710 Categorie: ,

pH Analog Controller with Self-Diagnostic Test – HI8710

645,00 + 22% IVA

9990 disponibili (ordinabile)

Guadagna 645 punti
Richiedi informazioni

HI8710 is a panel mounted pH controller with self-diagnostic test capabilities. Users can set: the setpoint for acid or alkaline dosage, the tolerance of the setpoint before an alarm is activated, the dosage mode: automatic, continuous on or OFF and the over dosage control by setting the overtime dosage knob.

  • Hanna’s exclusive Fail Safe Alarm System protects against risks typical of industrial environments
  • Temperature compensation ensures fast, accurately compensated readings
  • Backlit, LCD display for easy viewing
Tempi di spedizione
Non a stock, spedizione prevista entro 10 giorni lavorativi
Garanzia diretta dal produttore
Assistenza clienti sempre a disposizione
Maggiori informazioni
Specifiche tecniche
Recensioni
Downloads
Info Ordine

Fail Safe Alarm System

Hanna’s exclusive Fail Safe Alarm System protects against problems caused by power supply failure or signal interruption. An alarm condition is indicated by a red LED, located directly on the front panel of the controller.

Overtime Dosage

“Overtime dosage” function with selection knob and jumper for disable on the rear panel. If the dosing relay remains continuously activated for more than selected dosing time the alarm relay is activated, the alarm LED is blinking and the dosing relay is deactivated.

ORP Dosing Consent Device

When used in conjunction with the HI8720 ORP controller, the ORP Dosing Consent Device function will ensure that the ORP dosage will start only when the pH level is correct.

Automatic Temperature Compensation

A 2-wire Pt100 can be connected to provide automatic temperature compensation of the pH measurements.

Matching Pin Connection

Supports potential matching pin connection to avoid typical problems caused by grounding loop current, such as progressive damage of the electrode, fluctuating measurements, and poor process regulation.

Robust Design

A removable, transparent splash-proof cover protects the front panel.

Scala pH: 0.00 to 14.00 pH
Risoluzione pH: 0.01 pH
Accuratezza pH: ±0.02 pH (0 to 100 °C)/ ±0.05 pH (-20 to 0 °C) (electrode); ±0.5% (transmitter)
Calibrazione pH: Offset: ±2 pH with OFFSET trimmer; Slope: 80 to 110% with SLOPE trimmer
Compensazione della Temperatura pH: Fixed or automatic with Pt100 from -20 to 100 °C (-4 to 212 °F)
Set Point Relè Allarme: 1, isolated, 2 A, Max 240 V, resistive load, 1000000 strokes (not fuse protected)
Scala Relè Allarme: 0.2 to 3.00 pH
Segnale Ingresso Analogico: 4 to 20 mA
Segnale Uscita Analogica: 0-20 mA or 4-20 mA (isolated)
Retroilluminazione: Continuous ON
Voltaggio di Uscita: ±5 Vcc; 150 mA max load for amplified electrodes
Componenti Esterne Incluse: Black anodized aluminium body; front and back with ABS; transparent splash-proof front cover
Condizioni di Utilizzo: -10 to 50°C (14 to 122°F); RH max 95% non-condensing
Dimensioni: 141 x 69 mm (5.6 x 2.7'')
Peso: 1 kg (2.2 lb.)

Non ci sono download disponibili per questo prodotto
Non ci sono informazioni sull'ordine di questo prodotto